ELECTRICEU Safety Gate · 13 November 2026
Circuit breaker — RCCB RX3 2P 63A A 30MA
- Product
- RCCB RX3 2P 63A A 30MA
- Brand
- Legrand
- Hazard
- The measured trip threshold is higher than indicated (approximately 80 mA). The user could therefore receive an electric shock. The product does not comply with the requirements of the Low Voltage Directive nor with the European standard EN 61009-1.
- Action
- Type of economic operator taking notified measure(s): ManufacturerCategory of measure(s): Withdrawal of the product from the marketDate of entry into force: 04/08/2026Type of economic operator taking notified measure(s): ManufacturerCategory of measure(s): Recall of the product from end usersDate of entry into force: 04/08/2026
- Status
- Active until 13 November 2027
What to do
Don't consume it. Return it to the store for a refund or replacement, even without a receipt. If you have symptoms, contact a doctor.